Abstract
The paper describes a statistical procedure for determining the flashover probability of insulator chains at different voltages as a function of the pollution level and shows the effect of connecting insulators in parallel in a line. It also provides calculation methods to combine the flashover probability curve and the measured contamination level distribution curve, the results of which give the risk of failure of a line at different voltages. With the selection of the acceptable risk of failure, the new computerized method offers a more accurate design of transmission line insulation in polluted areas. The data for this calculation are based on a contamination survey, which gives the chemical composition of the contaminant, the probability of occurrence of a contamination level and its distribution probability, and on laboratory tests which give the 50% flashover voltage of the insulators together with the standard deviation of the measurements.
Original language | English (US) |
---|---|
State | Published - Jan 1 2017 |
Event | IEEE Power Eng Soc, Text of 'A' Pap from the Winter Meet - New York City, NY, USA Duration: Jan 25 1976 → Jan 30 1976 |
Other
Other | IEEE Power Eng Soc, Text of 'A' Pap from the Winter Meet |
---|---|
City | New York City, NY, USA |
Period | 1/25/76 → 1/30/76 |