Abstract
Previous researchers have shown, using FFT spectrum analyzers, that arcing causes a significant increase in the third harmonic content of the leakage current of polluted insulators. This paper investigates the feasibility of using modern high resolution digital spectral analysis methods to obtain better spectral estimates. Techniques discussed include the classical periodogram, correlogram, autoregressive (AR) and autoregressive-moving average (ARMA) methods. The leakage current was continuously acquired and stored (for about 30 mins) during flashover tests. The analog waveform was then digitized off-line and the digitized samples used to compute the power spectral density (PSD). It was observed that the relative magnitudes of the odd harmonics in the leakage current increase with increase in arcing intensity. In particular the third harmonic PSD increased from almost zero at the start of the experiment to about 20% of the fundamental frequency just prior to flashover.
Original language | English (US) |
---|---|
Title of host publication | Proceedings of the IEEE Power Engineering Society Transmission and Distribution Conference |
Place of Publication | Piscataway, NJ, United States |
Publisher | IEEE |
Pages | 806-811 |
Number of pages | 6 |
Volume | 2 |
State | Published - 1999 |
Event | Proceedings of the 1999 IEEE/PES Transmission and Distribution Conference - A Vision Into the 21st Century - New Orleans, LA, USA Duration: Apr 11 1999 → May 16 1999 |