Abstract
Feasible ranges of thermal conductivity and diffusivity for subsurface soils and borehole grouts were evaluated to determine their influence on the required length of ground heat exchangers (GHEs) for both horizontal and vertical Ground-Coupled Heat Pump (GCHP) systems in hot-arid regions (drylands). An integrated simulation framework combining EnergyPlus and Ground Loop Design (GLD) was used to model thermal loads for two prototype office buildings in Phoenix , Arizona, and to assess five ground heat exchanger (GHE) configurations. Results show that improving the thermal properties of the subsurface and grout materials can lead to substantial reductions in required trench or borehole length, significantly lowering installation costs and improving system efficiency for both horizontal and vertical systems. Enhanced grout conductivity further improves vertical system performance but can also contribute to long-term ground temperature rise, particularly in high-conductivity environments. This study identifies practical thermal property targets and highlights key trade-offs in system design, offering guidance for the deployment of efficient, low-water-use GCHP systems in hot-arid climates.
| Original language | English (US) |
|---|---|
| Article number | 117313 |
| Journal | Energy and Buildings |
| Volume | 360 |
| DOIs | |
| State | Published - Jun 1 2026 |
Keywords
- Drylands
- Ground heat exchanger (GHE)
- Ground-coupled heat pump (GCHP)
- Hot-arid climate
- Thermal conductivity
- Thermal diffusivity
ASJC Scopus subject areas
- Civil and Structural Engineering
- Building and Construction
- Mechanical Engineering
- Electrical and Electronic Engineering
Fingerprint
Dive into the research topics of 'Feasibility of ground coupled heat pump systems for cooling in hot-arid regions: the role of thermal properties and system configurations'. Together they form a unique fingerprint.Cite this
- APA
- Standard
- Harvard
- Vancouver
- Author
- BIBTEX
- RIS